Technical Information

Technical information and frequently asked questions

The key dimensions, protection classes, product codes and answers to the most common questions you need when choosing and installing a rack cabinet, all on one page.

Key Concepts

Rack cabinet dimensions you should know

A few basic concepts are all you need to choose the right cabinet.

1U = 44.45 mm

U height

Rack cabinet and device heights are measured in “U”. 1U equals 44.45 mm (1.75 in); a 42U cabinet has 42 mounting positions of 1U each.

482.6 mm

The 19-inch standard

The front panel of 19" rack devices is 482.6 mm wide. The mounting rails of Racksis® cabinets are positioned to this dimension in line with IEC 60297-1.

290 – 1000 mm

Depth

Cabinet depth must cover the deepest device plus cable space at the rear. Our products range from 290 mm in Open Frame to 1000 mm in the Server and Network series.

600 / 800 mm

Width

19" devices fit a 600 mm wide cabinet. An 800 mm width leaves room at the sides for vertical cable organisers and cable trays.

20 – 1000 kg

Static load

The total equipment weight the cabinet can carry. Across our series it ranges from 20 kg in Slim to 1000 kg in Active.

IP20 – IP66

Protection class

The IP code shows the cabinet's level of protection against solid objects and water. Indoor cabinets are IP20; outdoor cabinets are IP54 or IP66.

The cabinet's external height is greater than this because of the plinth, feet and top cover. The external height of every model is in the table on its series page.
IP Protection Classes

What do IP20, IP54 and IP66 mean?

The first digit of the IP code shows protection against solid objects and dust, the second against water (IEC 60529).

IP20
2
Protected against solid objects larger than 12.5 mm (e.g. fingers)
0
No protection against water
Indoor: Slim, Soho, Silver, Eco Standing, Network, Active and Server series
IP54
5
Dust protected; dust ingress does not interfere with operation
4
Protected against splashing water from any direction
Outdoor: IP54 versions of outdoor standing, wall and pole cabinets (O-ring lock)
IP66
6
Dust-tight
6
Protected against powerful water jets
Harsh outdoor: IP66 versions of outdoor cabinets (3-point espagnolette lock)
Series Table

Technical summary of all series

Dimensions, load, protection, colour and delivery information for every Racksis® series in one place. Detailed sizes and product codes are on the series pages.

SeriesHeightW × D (mm)LoadProtectionStandard colourDelivery
Slim Series3U+2U · 5U+3USee series page20 kgIP20RAL 7035Assembled
Soho Series4U – 12U520 × 400 / 56040 kgIP20RAL 7035Flat-packed
Silver Series7U – 12U600 × 450 / 60080 kgIP20RAL 9005Flat-packed
Hyper Series6U – 20U600 × 450 / 600150 kg—RAL 9005 / 7035Assembled / flat-packed
Eco Standing Series16U – 26U600 × 450 / 600100 kgIP20RAL 9005Flat-packed
Network Series16U – 47U600 / 800 × 600 – 1000800 kgIP20RAL 9005Assembled / flat-packed
Active Series26U – 47U800 × 800 / 10001000 kgIP20RAL 9005Assembled / flat-packed
Server Series26U – 47U800 × 1000Ask usIP20RAL 9005Assembled / flat-packed
Open Frame Series26U – 47U540 × 290 – 950100 kg—RAL 9005 / 7035Assembled / flat-packed
Outdoor Standing Type16U – 26U600 × 450 / 600150 kgIP54 / IP66RAL 7035Assembled
Outdoor Wall Type7U – 12U600 × 450 / 600100 kgIP54 / IP66RAL 7035Assembled
Outdoor Pole Type12U – 20U600 × 450 / 600100 kgIP54 / IP66RAL 7035Assembled

Load values are static loads. Please ask us about the load capacity of the Server series.

FAQ

Frequently asked questions

Product selection

How do I choose the right cabinet for my project?

Installation location, required U height, depth of the deepest device, cable density and total equipment weight are the five criteria that define the choice.

The Cabinet Selector uses these criteria to suggest matching models from our catalogue, together with their product codes.

What is the difference between wall mount and floor standing cabinets?

Our wall mount cabinets are produced from 4U to 20U (3U+2U and 5U+3U in the Slim series) for floor distribution, offices, retail and CCTV, where there are only a few devices.

Floor standing cabinets are produced from 16U to 47U and are designed for server rooms, data centres and dense network infrastructure.

Which series do you recommend for servers?

The Server Series is designed for server and storage systems: 800 × 1000 mm, 80% perforated doors (single wing at the front, double wing at the rear), 8 omega carriers in 2 mm galvanised steel and M16 levelling feet.

For very heavy equipment, the Active Series offers a static load capacity of 1000 kg.

When should I choose an Open Frame rack?

Open Frame racks are for multicore cabling systems that need no doors or panels. With no doors or panels, natural ventilation is at its maximum, and the flat-pack design lowers transport and storage costs.

They are produced from 26U to 47U, in single frame depths of 290 and 370 mm and double frame depths of 550, 750 and 950 mm.

Which cabinet should I choose for outdoor use?

Our outdoor cabinets come in three mounting types: on the ground (16U–26U), on a wall (7U–12U) and on a pole (12U–20U).

All are produced in IP54 or IP66, with a galvanised steel body and outdoor polyester paint. Double hull models have 10 mm glass fibre insulation that better protects equipment from ambient temperature and humidity.

Which cabinet suits a small or home office?

The Soho Series is designed for small network and CCTV applications, with heights of 4U–12U, depths of 400 and 560 mm, a lockable glass front door and 2 fan slots.

For tight spaces where appearance matters, see the slim Slim Series.

Technical details

How many millimetres is 1U?

1U = 44.45 mm (1.75 in). Cabinet height is given in U; a 42U cabinet, for example, has 42 positions of 1U.

The cabinet's external height is greater than the U total because of the plinth, feet and top cover. You can find the external height of every model in the dimension table on its series page.

What does the 19-inch standard mean?

The front panel of 19" rack mount devices is 482.6 mm wide, and cabinet mounting rails are positioned to this dimension.

Racksis® products are designed in line with IEC 60297-1 (19" rack dimensions) and IEC 60917 (modular order).

What is the load capacity of your cabinets?

Static load capacities of our series:

  • Slim 20 kg · Soho 40 kg · Silver 80 kg · Hyper 150 kg
  • Eco Standing 100 kg · Open Frame 100 kg
  • Network 800 kg · Active 1000 kg
  • Outdoor standing 150 kg · Outdoor wall and pole 100 kg

Please ask us about the load capacity of the Server series.

What is the difference between IP20, IP54 and IP66?

IP20 protects against finger-sized objects but offers no protection against water; our indoor cabinets are in this class. IP54 protects against dust and splashing water, and IP66 is dust-tight and protected against powerful water jets.

IP54 versions of our outdoor cabinets use an O-ring lock, IP66 versions a 3-point espagnolette lock. IP protection classes

What perforated door options are available?

A 63% perforated metal door option is available in the Silver, Hyper, Eco Standing, Network and Active series. In the Server series, 80% perforated doors are standard: single wing at the front and double wing at the rear.

Can the door opening direction be changed?

The door opening direction can be changed in the Soho, Eco Standing and Server series. For other series, please ask us.

Which colours are available?

The standard colour of the Silver, Eco Standing, Network, Active and Server series is RAL 9005 black. Slim and Soho are RAL 7035 light grey; Hyper and Open Frame are produced in both RAL 9005 and RAL 7035. Outdoor cabinets have RAL 7035 outdoor polyester paint.

Please ask us about other colours.

Do the cabinets have an earthing connection?

An earthing connection from cabinet to front door is standard in the Silver, Hyper and Eco Standing series. Earthing bars are available as accessories for earthing inside the cabinet.

Installation and ventilation

How is the cabinet ventilated?
  • Soho, Silver and Eco Standing: 2 fan slots on top
  • Network and Active: 4-fan unit slot as standard; 6-fan units can also be used
  • Server: vented top cover for a 6-fan unit and 80% perforated doors
  • Outdoor: 2-fan unit slot in the roof and filtered extra fan slots on the sides

For projects with a high heat load, see our cooling systems.

Can a wall mount cabinet stand on the floor?

Yes. Silver sizes of 9U and above, and Hyper sizes of 12U, 16U and 20U, can be used on the floor with optional levelling feet or a castor set.

Conversely, the floor standing Eco Standing cabinet can also be mounted on a wall with 4 brackets.

How do cables enter the cabinet?

The Soho, Silver, Hyper and Eco Standing series have knock-out cable entry plates in the top, bottom and rear covers; the Slim series has them at the top and sides. The Network, Active and Server series have a 220 × 178 mm sliding cable entry in the bottom sheet, with brushed entry options.

In outdoor cabinets, a fully gasketed flange plate keeps the protection class intact at the cable entry.

Can I fix the cabinet to the floor?

The base of the Active series is pre-drilled for floor fixing. Open Frame comes with 2 × 3 mm L plates for floor fixing. M10 levelling feet are standard on Eco Standing, M16 on Active and Server.

For extra protection against tipping, an anti-tilt block can be used.

Why use blanking panels?

Blanking panels close empty U positions in the cabinet. This stops hot air from devices returning to the front, directs cool air through the devices and keeps the front of the cabinet tidy.

Blanking panels

Ordering and delivery

Are products delivered assembled?
  • Assembled: Slim and all outdoor cabinets
  • Flat-packed (single box): Soho and Silver; Eco Standing can also be delivered assembled on request
  • Assembled or flat-packed on request: Hyper, Network, Active, Server and Open Frame

For outdoor wall and pole cabinets, mounting parts must be specified in the order.

How do I build a product code?

A product code is made up of the series, height, width × depth and your door, cable entry, colour or protection class choices. Use the option tables on the series pages or leave the choice to us at the quote stage. Product code examples

How can I get a quote?

Fill in the quote form, or add the models you choose in the Cabinet Selector to your quote list and send your request directly.

Can you make non-standard sizes or manufacture under our brand?

For project-specific configurations and manufacturing under your own brand, see our OEM Manufacturing page. Requests are evaluated project by project.

Where can I download the product catalogue?

The current product catalogue is available on the Catalogue page.

Can I become a Racksis® dealer?

To apply as a dealer or distributor, fill in the form on the Become a Partner page.

Quality and standards

Which standards do your products comply with?

Our products are designed and manufactured in line with IEC 61587-1:2017 (cabinets for electronic equipment), IEC 60917 (modular order) and IEC 60297-1 (19" rack dimensions); they are RoHS compliant and CE marked.

Which management system certificates do you hold?

We hold ISO 9001:2015 quality, ISO 14001:2015 environmental and ISO 45001:2018 occupational health and safety management system certificates. Quality and Certificates

Where are the products manufactured?

Racksis® cabinets are manufactured under one roof in our 12,000 m² facility in İzmit, Kocaeli, with CNC bending, electrostatic powder coating and assembly.